Tiếng việt

On Stock 0 Products

Tyco Sprinkler System

Alarm Check Valve
  • Alarm Check Valve
  • Alarm Check Valve
  • Alarm Check Valve

Alarm Check Valve

  • Product’s code: AV-1-300
  • Brand: Tyco
  • Guarantee: 1 Year
  • Status: 1
  • Price: Please contact us!
  • Promotion Price: Please contact us!
Choose Products Review Your Cart Save Your Products
  • Product’s Introduction
  • Specifications
  • CATALOG
  • Accessories
  • Model AV-1-300 Alarm Check Valve, 300 psi (20,7 bar) 2-1/2, 4, 6, & 8 Inch (DN65, DN100, DN150 & DN200) Vertical or Horizontal

    The TYCO Model AV-1-300 Alarm Check Valves are divided seat ring, rubber-faced clapper, waterflow alarm check valves that are intended for use in wet pipe (automatic sprinkler) fire protection systems. They may be installed vertically or horizontally*, and they are designed to automati­cally actuate electric and/or hydraulic alarms when there is a steady flow of water into the system that is equivalent to the discharge rate of one or more sprinklers.

    A separately ordered Model RC-1 Retard Chamber (TFP920) is required for installations subject to variable pressures. It is used to help prevent false alarms associated with pressure variations in public water supplies.

    The AV-1-300 Alarm Check Valve Trim includes pressure gauges to monitor system pressure conditions, a by-pass check valve, a main drain valve, and an alarm test valve. The bypass check valve reduces the possibility of false alarms by permitting slow as well as small transient increases in water supply pressure to be passed through to the system without opening the waterway clapper.