The Cooper CF3000 is a high specification intelligent addressable control panel which is available in various loop configurations. These panels combine sophisticated functionality with simple operation and an aesthetically pleasing design.
The large capacity, ability to support complex cause and effect programming and wide range of user controllable functions make the system suitable for a diverse range of projects from sheltered housing to large office developments.
The CF3000 uses soft addressing to minimise installation time and remove the potential for error associated with manual addressing. It can operate as a stand alone panel or as part of a networked system. They have powerful programming options that allow configurable control over whether messages from specific panels are transmitted around the network or remain local.
An extensive range of compatible intelligent addressable systems ancillaries are available to work with the CF3000 all of which incorporate an integral short circuit isolator to provide maximum protection against short circuits on the external loop.
CF30001G | 1-Loop panel |
CF30002G | 2-Loop panel |
CF30004G | 4-Loop panel |
CF30001GP | 1-Loop panel c/w integral printer |
CF30002GP | 2-Loop panel c/w integral printer |
CF30004GP | 4-Loop panel c/w integral printer |
CF30001GNC | 1-Loop panel c/w network card |
CF30002GNC | 2-Loop panel c/w network card |
CF30004GNC | 4-Loop panel c/w network card |
CF30001GPNC | 1-Loop panel c/w integral printer, network card |
CF30002GPNC | 2-Loop panel c/w integral printer, network card |
CF30004GPNC | 4-Loop panel c/w integral printer, network card |
Code | CF30001G | CF30002G | CF30004G |
Description | 1 Loop Control Panel | 2 Loop Control Panel | 4 Loop Control Panel |
Standards | EN54 Pt2, 1997, A1:2006, EN54 Pt4, 1997, A1:2002, A2:2006 EN54 Pt13: 2005 | ||
Specification | |||
Number of Loops | 1 | 2 | 4 |
Addresses per Loop | 200 | ||
Number of conventional sounder circuits | 4 monitored for open and short circuit | ||
Auxiliary Fire Routing Equipment Output (Monitored) | 24V 30 mA (max) | ||
Auxiliary Fault Protection Equipment Output (Monitored) | 24V 30 mA (max) | ||
Auxiliary Fault Routing Equipment Output (Monitored) | 12V 30 mA | ||
System Operating Voltage | 24V dc (nom) | ||
Mains Input Supply | 230V ac +1%/-15% | ||
Class Change Facility | Terminals for connection of external contacts, can also be instigated via input interface | ||
Auxiliary Relay | 1 set of changeover contacts operate in event of fire condition | ||
Output Ports | RS485, RS232 for connection of repeaters etc | ||
Standby Duration | Dependent on loop loading and battery configuration | ||
Battery | 2 x 12Ah (standard versions) | 2 x 12Ah (standard versions) 4 x 12Ah (EB versions) | 2 x 12Ah (standard versions) 4 x 12Ah (EB versions) |
Environmental | |||
Operating Temperature | -5OC - +40OC | ||
Humidity (Non Condensing) | 0 to 75% RH | ||
Physical | |||
Construction | Back – Box – Mild Steel, Front Door – PC/ABS | ||
Dimensions (HxWxD) | Standard Versions: 397mm x 497mm x 180mm | Standard Versions: 397mm x 497mm x 180mm EB Versions: 397mm x 497mm x 280mm | |
Weight | 18kg | ||
Ingress Protection | IP30 | ||
Cable entries | Top: 31 cable knockouts (20mm) Back: 12 cable knockouts (20mm) | ||
System Networking | Fully networkable up to 126 panels (requires additional network card – 1 per panel) |