Addressable, completely bus supplied and short circuit / open circuit resilient alarm signaling device for optical alarm signaling. Its flat and unobtrusive design enables optimum adaptation to the environments.
Features:
Completely bus supplied alarm device
Powered loop compatible
5 different signaling device types - acoustic - optical- acoustic / optical- acoustic / optical- acoustic / optical / speech
Multilingual speech alarm in 5 different languages
Alarm signaling, evacuation, and test alarm can each be programmed in different languages
Up to 32 alarm devices for each powered loop
Each alarm device has built-in isolator
Acoustic alarm signaling:
Acoustic pressure up to 99 dB(A) @ 1 m
Volume programmable in 8 steps via tools 8000
20 different signaling tones, including DIN tone
Speech alarm, 5 pre-programmed alarm texts and other country-typical alarm signals
Flash intensity equivalent to 3W Xenon flash light
Light intensity: max. 3.87 cd effective, max. 24 cd peak
- Operating voltage : 8 ... 42 V DC (via powered loop)
- Quiescent current @ 19 V DC : approx. 55 μA
- Quiescent current @ FACP battery : approx. 300 μA @ 42 V
- Sound level : 97 dB(A) +/- 2 dB @ 1 m
- Strength of light : max. 24 cd peak/ 3.87 cd effective
- Frequency of flash : approx. 1 Hz
- Lighting energy : approx. 3 Y
- Ambient temperature : -10 °C ... 50 °C
- Type of protection : IP 30
- (IP65 with socket 806201 / 806202)
- Housing : ABS plastic
- Air humidity : <95 %
- Color : base: white, similar RAL 9010
- cap: amber/ blue, green, transparent/ red
- Weight : approx. 300 g
- Dimensions : Ø: 112 mm D: 75 mm
Ø: 112 mm D: 90 mm (with IP 65 socket)