The
The first address on the
The supervised state (normal, open, or short) of the moni- tored device is sent back to the panel. A common SLC input is used for all modules, and the initiating device loops share a common supervisory supply and ground — otherwise each monitor operates independently from the others.
Each
NOTE: Unless otherwise specified, the term
Standby current: 3.5 mA (SLC current draw with all addresses used; if someaddresses are disabled, the standby current decreases).
Alarm current: 55 mA (assumes all tenLEDs solid ON).
Temperature range: 32°F to 120°F (0°C to 49°C) for UL applications;
Humidity: 10% to 85% noncondensingfor UL applications; 10% to 93% noncondensing for EN54 applications.
Dimensions: 6.8" (172.72 mm)high x 5.8" (147.32 mm) wide x 1.25" (31.75 mm) deep.
Shipping weight: 0.76 lb. (0.345 kg) including packaging.
Mounting options:
–
–
–
–
–EQ CabinetSeries: See
Wire gauge: 12 AWG (3.31 mm²) to 18AWG (0.821 mm²).
Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent.
Maximum IDC wiring resistance: 1500 ohms.
Maximum IDC voltage: 10.2 VDC.
Maximum IDC current: 240 µA.