The 800 series are 2-wire conventional low profileplug-in detectors designed to meet theperformance criteria designated by UL. It is a low cost and high reliabilityseries. A LED will be latched on to locally indicate alarm. The in (-) and out(-) terminals are short-circuited inside the detectors. When the detector ismounted , it will continue the wire to the next device or EOL resistor. When itis removed, the wire will be open for wiring supervision.
881 Model 881 is a 2-wire conventional ionization smokedetector that uses a state-of-the-art sensing chamber. These detectors aredesigned to provide open area protection and to be used with compatible ULlisted panels only.
882 Model 882 is a 2-wire conventional photoelectronic smoke detector that use astate-of-the-art optical sensing chamber. This detector is designed to provideopen area protection and to be used with compatible UL listed panels only.
885 Model 885 is a 2-wire conventional fixed temperature heat detector. These detectors aredesigned to provide open area protection and to be used with compatible ULlisted panels only.
The 800 series are UL listed.
Size
Height(With base): 5.5 cm (Ionization), 4.8cm (Heat), 5.0cm (Photoelectronic)
Diameter :10.2 cm
Operating Temperature Range :32°F to 100°F (0°C to 38°C) for heat,32°F to 120°F (0°C to 49°C)
for lonization, photoelectronic
Operating Humidity Range :5%-95%RH
Latching Alarm :Resetby momentary power interruption
Max Air Velocity :4000ft/min (Photoelectronic),2000ft/min (Ionization)
Operating Voltage: 15~ 30VDC
Standby Current: <= 50 µA
Alarm Current: min2mA @ 3.1VDC
max 80mA @ 6.5VDC
Maximum Ripple Voltage: 4 Volts peak to peak
Sensitivity: 145°F (63°C)heat only