A comprehensive range of conventional detectors are available to operate with the Cooper conventional panel range.
Model (UNB) | CPD321 | CPT341 | CFR330 | CMT360 | CHT390 |
Description | Optical Sensor | Photo-Themal Sensor | Heat Sensor (Fast) | Heat Sensor (Med) | Heat Sensor (High) |
CPD approved product | 0832CPD0633 | 0832CPD0629 | 0832CPD0233 | 0832CPD0236 | 0832CPD0237 |
Standards | EN54 pt7:2000 | EN54 pt7:2000 | EN54 pt5:2000 + A1:2002 | ||
+ A1:2002 | + A1:2002 | | | | |
| EN54 pt5:2000 | | | | |
| + A1:2002 | | | | |
Area coverage | 100m² (subject to local standard) | 50m² (subject to local standard) | |||
System wiring | 2 core | ||||
Indication | 360° visibility light pipe | ||||
Mounting | Surface mount CDBB300, FXN520 base | ||||
Compatibility | Conventional fire panels | ||||
Detetion Mode | Light scatter principle | Light scatter principle | Heat sensitive element | ||
| heat sensitive element | | | | |
Operating voltage | 15 to 30V dc | ||||
Max stand by current | 30μA | ||||
Max Start up current | 340μA | | |||
Max alarm current | 25mA | ||||
Heat class | | A2S | A2R | BS | CS |
Alarm temperature | | 60°C | | 77°C | 92°C |
Environmental | | | | | |
Application | Indoor use IP 40 | ||||
Temperature | -20°C to 60°C | -20°C to 45°C | -20°C to 60°C | -20°C to 60°C | -20°C to 75°C |
Humidity | 0 to 95% non condensing | ||||
EMC | CE marked | ||||
Construction | | | | | |
Material | PC/ABS | ||||
Colour | White | ||||
Dimensions | | | | | |
Excluding Base (Dia x H) | | 100mm x 43mm | |||
Including Base (Dia x H) | 100mm x 45mm | 101mm x 55mm |