This range of intelligent addressable sensors have been specifically designed to operate with Cooper intelligent addressable fire systems.
All sensors are third party approved to the relevant section of EN54 (part 7 for smoke detectors & part 5 for heat detectors).
The optical sensor (CAP320) is suitable for most applications giving the fastest response to slow burning or smouldering fires which give rise to large visible smoke particles.
The photo-thermal sensor (CAPT340) will respond quickly to fast clean burning fires yet maintain the advantage of optical sensors when detecting smouldering fires. The thermal enhancement of this sensor allows a higher alarm threshold which provides a greater rejection of false alarms. The sensor will also raise an alarm at temperatures exceeding 60ºC.
The heat sensor (CAH330) can be set to one of 3 modes 77ºC / 92ºC and rate of rise. These sensors are designed to be used in environments where the ambient conditions might cause false alarms if smoke detection were to be used, for example where there is a high level of dust, fumes, steam or smoke under normal conditions.
CAP320 | Optical sensor |
CAPT340 | Photo thermal ‘Dual’ sensor |
CAH330 | Heat sensor |
CAB300 | Analogue sensor base |
CIR301 | Conventional remote indicator |
MRIAD | Addressable remote indicator |
Model | CAP320 | CAPT340 | CAH330 |
Standards | EN54 pt7:2000 + A1:2002 | EN54 pt7:2000 + A1:2002 | EN54 pt5:2000 + A1:2002 |
Area coverage | 100m² (subject to local standard) | 50m² (subject to local standard) | |
System wiring | Min. 1.5mm, 2 core loop or spur | ||
Indication | 360° visibility light pipe | ||
Mounting | Surface mount CAB300 base | ||
Compatibility | CF range of analogue panels | ||
Addressing mode | Auto address | ||
Operating voltage | 18 to 30V dc | ||
Max standby current | 220μA | ||
Max alarm current | 5mA | ||
Heat class | |||
Rate of rise | NA | A1S | A1R |
Fixed 60ºC | NA | NA | BS |
Fixed 90ºC | NA | NA | CS |
Alarm temperature (static) | |||
AIR | NA | 60ºC | 60ºC |
BS | NA | NA | 77ºC |
CS | NA | NA | 90ºC |
Environmental | |||
Application | Indoor use IP 40 | ||
Temperature | -20°C to 60°C | -20°C to 50°C | -20°C to 60°C |
Humidity | 0 to 95% non condensing | ||
Construction | |||
Material | PC/ABS | ||
Colour | White | ||
Dimensions | |||
(excl. Base) (mm) | 101 (Dia) x 33 (H) | 101 (Dia) x 43 (H) | 101 (Dia) x 43 (H) |
(incl. Base) (mm) | 104 (Dia) x 45 (H) | 104 (Dia) x 55 (H) | 104 (Dia) x 55 (H) |
Weight | 76g (without base) |