Two versions of the intelligent addressable loop powered reflective beam detectors are available in this range, the (MAB50R) with a range of up to 50 metres and the (MAB100R) with a range of 50 to 100 meters.
Both the (MAB50R) and the (MAB100R) are compatible with the Cooper range of intelligent addressable fire systems.
These intelligent addressable loop powered reflective beam detectors are extremely simple to install, they require no separate power supply, operate on a reflective principle and have a simple set up mode to enable easy and quick alignment during installation.
These units are designed to replace individual point detectors in large open areas such as warehouses.
Fire and fault conditions are signalled to the control panel using standard loop wiring so no additional interconnection required.
Code | MAB50R/MAB100R |
Description | Reflective Beam Detector |
Standards | EN54 Pt12 & Pt17 2002 |
Specification | |
Operating Voltage | 18V dc to 30V dc |
Quiescent Current | <5mA (no LED’s illuminated) |
Alarm Current | <9mA |
Alignment Current | <18mA |
Power up Time | 10 seconds (approx.) |
Operating Range | 5 to 50 meters (MAB50R) 5 to 100meters (MAB100R) |
Tolerance to Beam Alignment at 35% | Detector + 0.8O, Prism +5.0O |
Fire Alarm Thresholds | 2.50dB (25%) 3.74dB (35%) 6.02dB (50%) |
Optical Wavelength | 880nm |
Environmental | |
Operating Temperature | -10OC - +55OC |
Humidity (Non Condensing) | 0 to 93% RH |
Physical | |
Construction | PC/ABS |
Color | White |
Dimensions (HxWxD) | 210mm x 130mm x 120mm |
Weight | 0.8kg |
Ingress Protection | IP40 |
Compatibility | |
Suitable for use with | Cooper Intelligence Addressable Fire Systems |