Including housing and alarm indicator. For connection to a conventional detection zone.
If the glass pane is replaced with the optionally available plastic pane with reset function, the MCP can be reset from the outside using the key.
For the surface mounting of the MCP the surface mount base Part No. 704980 must be ordered separately, if the cable wasn't laid about a standard flush mount wall socket.
Type a definition - single action in accordance with EN 54-11 § 3.4.1
(excerpt taken from EN standard):
Manual fire alarm unit, for which the alarm status is automatically set (additional alarm triggering is not required) after the fragile element has been broken or its position has been changed.
- Operating voltage : 8 ... 30 V DC
- Quiescent current @ 9 V DC : approx. 0 μA
- Alarm current @ 9 V DC : typ. 9 mA
- Alarm display : red LED and yellow actuation indicator
- No. of detector/zone : 10 detectors per zone (according to VdS)
- Application temperature : -20 °C ... 70 °C
- Storage temperature : -30 °C ... 75 °C
- Connection terminal : max. 2.5 mm² (AWG 26-14)
- Type of protection : IP43, IP55 with cover 704965
- Housing : PC ASA plastic
- Color : red, similar to RAL 3020
- Weight : approx. 110 g
- Detector specification : EN 54-11, type A
- Dimensions : W: 88 mm H: 88 mm D: 21 mm
-
- 704980 Surface mount housing