The VESDA VLP is the most popular detector in the VESDA by Xtralisproduct range. Like all VESDA ASDs, it detects fire at the earliest possiblestage and reliably measures very low to extremely high concentrations of smoke.It has the world’s widest sensitivity range of 0.005 to 20% obs/m (0.0015 to 6%obs/ft ). VESDA VLP supports four configurable alarms (Alert, Action, Fire 1and Fire 2) and protects areas up to 2,000 m2 (20,000 sq. ft.).
Supply Voltage: 18 to 30 VDC
Sensitivity Range: 0.005 to 20% obs/m (0.0015 to 6% obs/ft)
Area Coverage (Maximum): 2,000 m2 (20,000 sq. ft.)
Maximum Pipe Length: Aggregate pipe length: 200 m (650 ft.),
Maximum Single Length: 100 m (325 ft.)
Total Number of Alarm Thresholds: 8 (Day/Night)
Relay Outputs: 7 relays
On-board Memory: Up to 18,000
(Max. Events)
Flow Sensor Circuit: 4
(one per pipe inlet)
Maximum No. of Holes: 100